上海荣计达仪器科技有限公司

咨询电话:137-6111-8616


养护室自动控制仪 养护室三件套 混凝土标养室控制仪

养护室自动控制仪是专业混凝土养护检测仪器, 养护室自动控制仪采用数字控制仪表,能准确控制养护室的温湿度,适用于各水泥厂,水泥制品厂及建筑公路施工单位,科研质检单位对标准养护室的温湿度控制,具有操作方便,控制准确等优点。

  • 型号: BYS-III

  • 产品参数
  • 型号: BYS-III

一、养护室自动控制仪产品简介:

养护室自动控制仪是**混凝土养护检测仪器, 养护室自动控制仪采用数字控制仪表,能准确控制养护室的温湿度,适用于各水泥厂,水泥制品厂及建筑公路施工单位,科研质检单位对标准养护室的温湿度控制,具有操作方便,控制准确等优点。

Product introduction of automatic control instrument for curing room:

The automatic control instrument of the curing room is the testing instrument for concrete curing. The automatic control instrument of the curing room uses digital control instruments, which can accurately control the temperature and humidity of the curing room. The unit's temperature and humidity control of the standard curing room has the advantages of convenient operation and accurate control.


二、养护室自动控制仪技术指标:

★控温范围:0-50℃    控温精度:20±2℃   控湿范围:≥90%(相对湿度)

★加热功率:3KW       制冷功率:<2KW(可自配备〈25匹单冷空调)

★加湿功率:60W       电源电压:220±10%V   电源频率:50±1Hz

★外形尺寸:500×285×900(控制仪)       350×420×600mm(主机)

Second, the technical indicators of the automatic control instrument of the conservation room:

★ Temperature control range: 0-50 ℃ Temperature control accuracy: 20 ± 2 ℃ Humidity control range: ≥90% (relative humidity)

★ Heating power: 3KW Refrigeration power: <2KW (can be equipped with <25HP single-cooled air conditioner)

★ Humidification power: 60W Power voltage: 220 ± 10% V Power frequency: 50 ± 1Hz

★ Dimensions: 500 × 285 × 900 (controller) 350 × 420 × 600mm (host)


三、养护室自动控制仪结构:

该控制仪由控制仪、大型负离子加湿器、不锈钢加热水箱和空调(自备)四大部分组成。其温湿度的控制均由数显仪表自动交换,无需人工控制。

Third, the structure of the automatic control instrument in the curing room

The controller consists of a controller, a large negative ion humidifier, a stainless steel heating water tank, and an air conditioner (provided). The temperature and humidity control are automatically exchanged by digital display instruments without manual control.


四、养护室自动控制仪工作原理:

★温控:当养护室的内温度高于温控仪的上限给定值时,控制系统即输出制冷信号,控制空调外接负载工作;反之,温度低于温控仪的下限给定值时,主机即加热,当达到控制要求时自动恢复到恒温状态,如此反复达到控制目的。

★湿控:当养护室内的湿度低于控制值时,控制系统输出加湿信号,控制主机加湿器工作,室内湿度达到要求后即自动停止工作。

Fourth, the working principle of the maintenance room automatic controller:

★ Temperature control: When the internal temperature of the curing room is higher than the upper limit of the temperature controller, the control system will output a refrigeration signal to control the external load of the air conditioner. On the contrary, when the temperature is lower than the lower limit of the temperature controller, The host is heated, and when it reaches the control requirements, it automatically returns to the constant temperature state, so it repeatedly achieves the control purpose.

★ Humidity control: When the humidity in the maintenance room is lower than the control value, the control system outputs a humidification signal to control the host humidifier to work. When the indoor humidity reaches the requirements, it will automatically stop working.


五、养护室自动控制仪操作规程:

★**先将控制仪固定在养护室外,选择A近位置将温湿度探头放入养护室内并且固定好,温湿度插头分别插在控制仪内的温湿度后面。

★然后将主机放于养护室A位置,用塑料水管将增湿器的进水口与自来水管连通,打开水龙头(常开小量)进水能自动控制,水位必须高于电热管,以免电热管脱水烧毁,加热加湿插头分别插在控制仪的插座上。

★空调器安装前需将控制系统拆掉,然后将压缩机的电源插头直接接在制冷插座上。

★在安装时必须接好地线,电源须经单用闸刀开关才能接至控制仪上。

★仪器安装结束后,**先调整温湿度仪给定值,温度给定21.5℃,湿度给定20.5℃。

Fourth, the working principle of the maintenance room automatic controller:

★ Temperature control: When the internal temperature of the curing room is higher than the upper limit of the temperature controller, the control system will output a refrigeration signal to control the external load of the air conditioner. On the contrary, when the temperature is lower than the lower limit of the temperature controller, The host is heated, and when it reaches the control requirements, it automatically returns to the constant temperature state, so it repeatedly achieves the control purpose.

★ Humidity control: When the humidity in the maintenance room is lower than the control value, the control system outputs a humidification signal to control the host humidifier to work. When the indoor humidity reaches the requirements, it will automatically stop working.


六、养护室自动控制仪注意事项:

★为了延长外接负载的使用寿命,控制仪的控制系统内的均设置内外回差,这并非故障现象,控制仪外壳必须可靠接地。

★加湿器内严禁缺水,以免将加热管、加湿器烧坏,进水阀不应关闭也不要开的过大。

★如果加热装置在升温时,每次工作超过半小时说明该养护室保温不良或容积太大,用户需另配加热器,控制信号可由控制仪引出。

★本控制仪应置于通风、干燥、平整、无腐蚀性介质的环境中使用。

★因质量问题而引起的故障,自出厂之日起负责保修半年。

★如果电压不稳定,必须安装稳压电源,本仪器电压220±10%。

Six, matters needing attention in the automatic control instrument of the conservation room:

★ In order to prolong the service life of the external load, the internal and external hysteresis are set in the control system of the controller. This is not a malfunction, and the controller housing must be reliably grounded.

★ Water shortage is strictly forbidden in the humidifier, so as not to burn the heating pipe and humidifier. The water inlet valve should not be closed or opened too large.

★ If the heating device is warming up, if it works for more than half an hour each time, it means that the curing room has poor insulation or the volume is too large. The user needs to equip the heater separately.

★ The controller should be used in a ventilated, dry, flat, non-corrosive medium.

★ For the failure caused by quality problems, we will be responsible for the warranty for half a year from the date of shipment.

★ If the voltage is unstable, a regulated power supply must be installed. The voltage of this instrument is 220 ± 10%.


养护室自动控制仪 养护室三件套 混凝土标养室控制仪
养护室自动控制仪是专业混凝土养护检测仪器, 养护室自动控制仪采用数字控制仪表,能准确控制养护室的温湿度,适用于各水泥厂,水泥制品厂及建筑公路施工单位,科研质检单位对标准养护室的温湿度控制,具有操作方便,控制准确等优点。